Flux pattern in 1000 kVA 11/.433 kV distribution transformer core to sinusoidal wave
View/ Open
Date
2010-10-16Author
Shahanom, Uthman
Ismail, Daut, Prof. Dr.
Dina Maizana, Maiz Ahmad, Ir.
Metadata
Show full item recordAbstract
A study was conducted using sinusoidal waveform
to capture flux pattern in CRGO M5 material in a
1000kVA 11kV 3 phase transformer core. It is found
that it takes about 180⁰ electrical degree cycle for a
pool of flux to migrate from one core limb to the other
two limb. The computed and experimental values at
1.7T flux density for the core losses had shown a
difference of 4.2 %. There are two loops of flux flow
exist at any phase( ωt) angle in the core. The hotspot
area of the core is near the inner core of the T joint
and along the core window. The 2D FEM software
used has satisfied and fulfill the objective of the work
interest.