dc.contributor.author | Ismail, Daut | |
dc.contributor.author | Dina Maizana, Maiz Ahmad | |
dc.contributor.author | Shuhaimi, Zakaria | |
dc.contributor.author | S. Uthman | |
dc.contributor.author | Soib, Taib | |
dc.date.accessioned | 2008-10-20T01:33:48Z | |
dc.date.available | 2008-10-20T01:33:48Z | |
dc.date.issued | 2006 | |
dc.identifier.citation | American Journal of Applied Sciences, vol. 3 (9), 2006, pages 1990-1992. | en_US |
dc.identifier.issn | 1546-9239 | |
dc.identifier.uri | http://dspace.unimap.edu.my/123456789/2433 | |
dc.description | Link to publisher's homepage at http://scipub.org/scipub/index.php | en_US |
dc.description.abstract | This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60° was 10%, 12% and 15% better than the
core with T-joint 45°, T-joint 23° and T-joint 90° respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in causing the differences in performance. | en_US |
dc.language.iso | en | en_US |
dc.publisher | Science Publications | en_US |
dc.subject | Transformer core | en_US |
dc.subject | Flux distribution | en_US |
dc.subject | Rotational flux | en_US |
dc.subject | 3rd harmonic flux | en_US |
dc.subject | Power loss | en_US |
dc.subject | Building factor (BF) | en_US |
dc.subject | Electric transformers | en_US |
dc.title | Comparison of losses and flux distribution in 3 phase 100 kVA distribution transformers assembled from various type of T-Joint geometry | en_US |
dc.type | Article | en_US |
dc.identifier.url | http://scipub.org/scipub/index.php | en_US |