Show simple item record

dc.contributor.authorMohd Rafi, Adzman
dc.contributor.authorLehtonen, Matti
dc.date.accessioned2013-01-09T01:39:08Z
dc.date.available2013-01-09T01:39:08Z
dc.date.issued2012
dc.identifier.citationInternational Review on Modelling and Simulations, vol. 5 (4), 2012, pages 1765-1772en_US
dc.identifier.issn1974-9821
dc.identifier.urihttp://www.praiseworthyprize.it/public/SUBSCRIBERS/IREMOS.html
dc.identifier.urihttp://dspace.unimap.edu.my/123456789/22908
dc.descriptionLink to publisher's homepage at http://www.praiseworthyprize.it/en_US
dc.description.abstractIn networks with unearthed or compensated neutral, earth fault signals consist of different frequency components, which result from charging and discharging of the network capacitances. The charge transient which usually is of higher amplitude and lower frequency than the discharge transient is most suitable for fault location. This paper discusses a method for estimating a single phase to ground fault location in radially operated unearthed distribution network. The proposed method is based on correlation of undamped charge transient frequency with the fault distance. The undamped complex frequency is defined from the development of single phase to ground fault bus impedance matrix of the circuit network in complex frequency domain. The accuracy of the method was tested using a simulation model and the network example with overhead lines. The analysis was performed using the EMTP-ATP software.en_US
dc.language.isoenen_US
dc.publisherPraise Worthy Prize S.r.l.en_US
dc.subjectCharge transienten_US
dc.subjectFault locationen_US
dc.subjectImpedance matrixen_US
dc.subjectUnearthed networken_US
dc.titleA method for ground fault distance computation in unearthed medium voltage distribution networken_US