Title: Testing of contactors under voltage sag and non-sinusoidal voltage conditions
Authors: Surya Hardi, Amrin
Ismail, Daut, Prof. Dr.
Muhammad Irwanto, Misrun
ismail.daut@unimap.edu.my
surya@unimap.edu.my
Keywords: Contactors
Non-sinusoidal supply
Point on wave
Sensitive curve
Voltage sag
Issue Date: 29-Nov-2010
Publisher: Institute of Electrical and Electronics Engineers (IEEE)
Citation: p. 683-688
Series/Report no.: Proceedings of the IEEE International Conference on Power and Energy (PECon 2010)
Abstract: Sensitivity of electromagnetic contactors for voltage sags and non-sinusoidal voltage supply has been carried out by laboratory testing. Effects of sag characteristics such as; sag magnitude, sag duration and point on wave of sag initiation to be considered on contactors behavior. Contactors are subjected to voltage sags of depth varying, sag duration varying 5 ms to 600 ms, different point on wave and under different non-sinusoidal conditions. A Schaffner Profline 2100 EMC has been used as sag generator to create sag characteristics. The results show that sensitivity curves of the contactors depend on sag magnitude, sag duration and point on wave, whereas influence of non-sinusoidal voltage is slightly different.
Description: Link to publisher's homepage at http://ieeexplore.ieee.org/
URI: http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=5697667&tag=1
http://dspace.unimap.edu.my/123456789/19132
ISBN: 978-142448946-6
Appears in Collections:Conference Papers
Ismail Daut, Prof. Dr.

Files in This Item:
File Description SizeFormat 
Testing of contactors under voltage sag and non-sinusoidal voltage conditions.pdf7.04 kBAdobe PDFView/Open


Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.