Show simple item record

dc.contributor.authorIsmail, Daut, Prof. Dr.
dc.contributor.authorDina Maizana, MT
dc.contributor.authorM., Ahmad
dc.date.accessioned2010-08-12T06:31:11Z
dc.date.available2010-08-12T06:31:11Z
dc.date.issued2009-06-20
dc.identifier.citationp.1-3en_US
dc.identifier.urihttp://dspace.unimap.edu.my/123456789/8622
dc.descriptionMUCEET 2009 is organized by Malaysian Technical Universities Network (MTUN) comprising of Universiti Malaysia Perlis (UniMAP), Universiti Tun Hussein Onn (UTHM), Universiti Teknikal Melaka (UTeM) and Universiti Malaysia Pahang (UMP), 20th - 22nd June 2009 at M. S. Garden Hotel, Kuantan, Pahang.en_US
dc.description.abstractThis paper describes the result of measurement of localised temperature rise on 100kVA 3phase distribution transformer assembled with 90o T-joint and mitred lap corner joint with stagger yoke with overlap length of 10mm. The measurement involves the initial temperature and last temperature after 20 minutes experiment. The temperature rises have been measured using no load test by arrays of thermistor on M5 (CGO) grades material of transformer core laminations. The localised temperature rise at the outer 90o T-joint is 0.075 oC/minutes and rises to be 0.095 oC/minutes at the inner 90o T-joint when the transformer core energized 1.5 T 50Hz. A small amount of flux deviation from the rolling direction occurs at the overlap.en_US
dc.language.isoenen_US
dc.publisherUniversiti Malaysia Pahang (UMP)en_US
dc.relation.ispartofseriesProceedings of the Malaysian Technical Universities Conference on Engineering and Technology (MUCEET) 2009en_US
dc.subjectTransformer coreen_US
dc.subjectTemperature riseen_US
dc.subjectThermistoren_US
dc.subjectMalaysian Technical Universities Conference on Engineering and Technology (MUCEET)en_US
dc.titleGradient temperature on 3Phase transformer core with staggered yoke with 90 T-jointen_US