Show simple item record

dc.creatorChai, Chang Yii
dc.date2017
dc.date.accessioned2023-03-07T02:23:11Z
dc.date.available2023-03-07T02:23:11Z
dc.identifier.urihttp://dspace.unimap.edu.my:80/xmlui/handle/123456789/78039
dc.descriptionDoctor of Philosophy in Electrical Systems Engineeringen_US
dc.description.abstractPower cable may suffer from insulation degradation after a certain period of time because of environment, mechanical and electrical factors. Partial discharge (PD) at void or cavity of power cable’s insulation will lead to the power system breakdown in the near future. Nowadays, many PD location devices had been invented to estimate PD location on power cable. New technology has enabled PD estimation to evolve from offline PD estimation to online PD estimation. Advanced signal processing technique can be implemented in those devices in order to estimate PD location accurately. In this thesis, segmented correlation trimmed mean (SCTM) algorithm is proposed to estimate PD location on medium voltage (MV) power cable. The algorithm uses segmented correlation technique and trimmed mean data filtering technique to enhance the accuracy of the estimated PD location. Two experiments have been performed to test the program execution time and accuracy against noise of the algorithm. The algorithm had been tested in Matrix Laboratory (MATLAB) environment which consists modelled PD signals and different levels of white Gaussian noise (WGN) and discrete spectral interference (DSI). Discrete wavelet transform (DWT) de-nosing technique has been used for noise suppression. The first experiment is performed by increasing the sampling number of measured signal while recording the program execution time of the algorithm. The second experiment is performed by increasing the level of WGN and DSI while recording the maximum percentage error of the estimated PD location. The results from both experiments are compared with the existing multi-end correlation (MEC) algorithm. The results shown that the SCTM algorithm has longer time but lower maximum percentage error of the estimated PD location than MEC algorithm. In conclusion, SCTM algorithm is more suitable to apply in PD location estimation system for power cable due to its lower maximum percentage error.en_US
dc.language.isoenen_US
dc.publisherUniversiti Malaysia Perlis (UniMAP)en_US
dc.rightsUniversiti Malaysia Perlis (UniMAP)en_US
dc.subjectElectric dischargesen_US
dc.subjectCurrent transformers (Instrument transformer)en_US
dc.subjectElectric instrument transformersen_US
dc.subjectChemical detectorsen_US
dc.subjectPower cableen_US
dc.subjectPartial discharge (PD)en_US
dc.titlePartial discharge detection and location technique based on segmented correlation trimmed mean algorithm for power cableen_US
dc.typeThesisen_US
dc.contributor.advisorMuzamir, Isa, Assoc. Prof. Dr.
dc.publisher.departmentSchool of Electrical Systems Engineeringen_US


Files in this item