Show simple item record

dc.contributor.authorAsmarashid, Ponniran
dc.contributor.authorNor Akmal, Mohd. Jamail
dc.contributor.authorNor Anija, Jalaludin
dc.date.accessioned2010-08-17T02:51:24Z
dc.date.available2010-08-17T02:51:24Z
dc.date.issued2009-06-20
dc.identifier.citationp.42-46en_US
dc.identifier.urihttp://dspace.unimap.edu.my/123456789/8720
dc.descriptionMalaysian Technical Universities Conference on Engineering and Technology organized by Universiti Malaysia Pahang in collaboration with Universiti Tun Hussein Onn Malaysia, Universiti Teknikal Malaysia Melaka & Universiti Malaysia Perlis on June 20th - 22nd, 2009, at MS Garden Hotel, Kuantan, Pahang, Malaysia.en_US
dc.description.abstractThere are several appropriate techniques can be used in order to show the characteristics of aged and unaged underground XLPE cables after sometime in service. From the characteristics, performance of the cables can be evaluated. One of the techniques is based on tan delta and capacitance measurements of the cable insulation. This study focuses on underground XLPE cables which rated at 11 kV for both 1-core and 3-core types. Tan delta and capacitance data of underground XLPE cables are obtained using a Schering bridge instrument. The measurements are performed at the temperature about 29oC and 50 Hz power frequency. The analysis of data shows that tan delta values are increased in proportion to the aging factors and voltage stressed. Meanwhile the capacitance values of the cable insulator are increased and decreased in proportion to the aging factors and voltage stressed. Therefore, tan delta and capacitance are the useful parameters for evaluating the quality of underground XLPE cables insulator.en_US
dc.language.isoenen_US
dc.publisherUniversiti Malaysia Pahangen_US
dc.relation.ispartofseriesProceedings of the Malaysian Technical Universities Conference on Engineering and Technology (MUCEET) 2009en_US
dc.subjectTan deltaen_US
dc.subjectCapacitanceen_US
dc.subjectUnderground XLPE cablesen_US
dc.subjectSchering Bridgeen_US
dc.subjectCablesen_US
dc.subjectMalaysian Technical Universities Conference on Engineering and Technology (MUCEET)en_US
dc.titleTan delta and capacitance characteristics of underground XLPE cables – 11 kVen_US
dc.typeWorking Paperen_US


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record