Show simple item record

dc.contributor.authorIsmail, Daut, Prof. Dr.
dc.contributor.authorAhmad, D. M. M.
dc.date.accessioned2010-08-06T08:01:07Z
dc.date.available2010-08-06T08:01:07Z
dc.date.issued2009-09-07
dc.identifier.citationp.205-208en_US
dc.identifier.isbn978-0-8898-6807-6
dc.identifier.urihttp://www.actapress.com/Abstract.aspx?paperId=35462
dc.identifier.urihttp://dspace.unimap.edu.my/123456789/8502
dc.descriptionLink to publisher's homepage at http://www.actapress.com/en_US
dc.description.abstractThis paper describes the result of measurement of normal flux distribution 3-phase 100kVA transformer core assembled with 450T-joint. The investigation involves the variation of normal flux distribution in the core lamination. The normal flux distribution has been measured using no load test by arrays of search coil. The highest normal flux distribution occurs at the corner edge of the centre limb that is 0.160T and lowest at upper edge of yoke that is 0.121T. The average value of normal flux distribution is high at flux transfer region of the lamination. The flux transfer mechanism shows that two separate path flowing horizontally in the yoke before leaving the lamination to vertically adjacent layer and combine with the flux in that layer. Then, it will transfer back to origin region and extend through the centre limb.en_US
dc.language.isoenen_US
dc.publisherACTA Pressen_US
dc.relation.ispartofseriesProceedings of the 9th European Conference on Power and Energy Systems (EuroPES) 2009en_US
dc.subjectFundamental fluxen_US
dc.subjectGrain oriented silicon ironen_US
dc.subjectNormal flux distributionen_US
dc.subjectTransformer coreen_US
dc.subjectPower and Energy System 2009en_US
dc.titleNormal flux distribution in 45o T-joint of three phase transformer core with staggered yoke and limb10mmen_US
dc.typeWorking Paperen_US


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record