    Metallurgical failure analysis of a closed recirculation system water cooling pipe

    Thumbnail
    View/Open
    Metallurgical failure analysis of a closed recirculation system.docx (13.92Kb)
    Date
    2013
    Author
    Mohd Arif Anuar, Mohd Salleh
    Shaiful Rizam, Shamsudin
    Azmi, Kamardin
    Noor Hamidi, Mohd Noor
    Hafizan, Hassan
    Metadata
    Show full item record
    Abstract
    Catastrophic failure is often associated with a large temperature rise. This situation may lead to a drastic deterioration in material strength where a cooling system is important for a smooth system plant operation to prevent catastrophic failure to its equipments, parts or processes. In this study, a part of a failed closedrecirculation system water cooling pipe in a steel manufacturing plant in Malaysia has been investigated for detailed failure analysis. A steam leakage of a water cooling pipe with a closed recirculation system operation made of ASTM A106/A (Carbon Steel Pipes for high temp service) was detected. The aim of this study is to explore the evidence related to the water cooling pipe leakage and to investigate the cause of failure. Detailed investigation was carried out by visual inspection, optical microscopy and hardness testing. With the evidence obtained, due to presence of water scale and prolonged overheating, decarburization had occurred. During decarburization, it was found that carbon elements from inner surface tube had depleted through the outer tube surface. The accumulation of carbon elements on the outer tube surface appears to show significantly higher brittle zone in the outer tube and with the presence of tensile stress developed from operating thermal cycle which subsequently resulted in crack. It can be concluded that the water cooling pipe leakage was due to thermal fatigue.
    URI
    http://www.scientific.net/AMR.795.474
    http://dspace.unimap.edu.my:80/dspace/handle/123456789/34826
    Collections
    • Azmi Kamardin [10]
    • Mohd Arif Anuar Mohd Salleh, Associate Professor Dr. Ir. [43]

    Atmire NV

    Perpustakaan Tuanku Syed Faizuddin Putra (PTSFP) | Send Feedback
     

     

    Browse

    All of UniMAP Library Digital RepositoryCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsThis CollectionBy Issue DateAuthorsTitlesSubjects

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    Atmire NV

    Perpustakaan Tuanku Syed Faizuddin Putra (PTSFP) | Send Feedback