Please use this identifier to cite or link to this item: http://dspace.unimap.edu.my:80/xmlui/handle/123456789/34251
Title: Effect different limb of transformer core assemble on performance
Authors: Dina Maizana, Maiz Ahmad, Ir.
Mohd Afif, Mohd Radzi
Nuriziani, Hussin
dina@unimap.edu.my
mamr.afif@ygmail.com
nuriziani@unimap.edu.my
Keywords: 3%SiFe
Copper loss
Core loss
Flux density
Limb
Issue Date: 2014
Publisher: Trans Tech Publications
Citation: Key Engineering Materials, vol.594-595, 2014, pages 1136-1140
Abstract: This paper described the performance of transformer affected by different limb assembling. The experiment that used to investigate core is no-load, short circuit and load test to find the core loss, copper loss, flux leakage at corner joint and limb and total harmonic distortion of the flux at flux density range from 0.2 T to 1.6 T, 50 Hz. From the result of this investigation shows the core loss of transformer assembled with 2 limbs is 18.45% and 32.21% better than the transformer assembled with 3 and 5 limbs respectively at a flux density of 1.6T, 50 Hz. To increase the numbers of core limb assemble will reduce the efficiency of transformer.
Description: Link to publisher's homepage at http://www.ttp.net/
URI: http://dspace.unimap.edu.my:80/dspace/handle/123456789/34251
ISSN: 1662-9795
Appears in Collections:Dina Maizana Maiz Ahmad, Ir.
Nuriziani Hussin, Dr.
School of Electrical Systems Engineering (Articles)

Files in This Item:
File Description SizeFormat 
Effect different limb of transformer core assemble on performance.pdf129.9 kBAdobe PDFView/Open


Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.