Please use this identifier to cite or link to this item: http://dspace.unimap.edu.my:80/xmlui/handle/123456789/32440
Full metadata record
DC FieldValueLanguage
dc.contributor.authorMohd Rafi, Adzman-
dc.contributor.authorTopolánek, David-
dc.contributor.authorLehtonen, Matti I.-
dc.contributor.authorToman, Petr-
dc.date.accessioned2014-03-09T04:50:35Z-
dc.date.available2014-03-09T04:50:35Z-
dc.date.issued2013-10-
dc.identifier.citationInternational Review of Electrical Engineering, vol. 8(5), 2013, pages 1520-1531en_US
dc.identifier.issn1827-6660-
dc.identifier.urihttp://www.praiseworthyprize.com/IREE-latest/IREE_vol_8_n_5.html-
dc.identifier.urihttp://dspace.unimap.edu.my:80/dspace/handle/123456789/32440-
dc.descriptionLink to publisher's homepage at http://www.praiseworthyprize.com/en_US
dc.description.abstractThis paper proposes a scheme to locate an earth fault in an unearthed or a compensated neutral medium voltage (MV) network using the transient signal recorded from MV/LV substations. The algorithm applies continuous wavelet Transform (CWT) to locate the dominant charge transient frequency and then fast Fourier transform (FFT) to extract coefficients to be used in the fault location scheme. The fault location scheme managed to identify the correct path of fault location towards the position of the fault using the transient signal recorded from secondary side of the LV substation transformers. The results from intensive simulations and experiments in actual distribution network are also presented in this paper. The final results show that the fault location scheme is able to locate and identify the correct fault location successfully.en_US
dc.language.isoenen_US
dc.publisherPraise Worthy Prize S.r.l.en_US
dc.subjectCharge transienten_US
dc.subjectCompensated networken_US
dc.subjectContinuous wavelet transform (CWT)en_US
dc.subjectEarth faulten_US
dc.subjectFault locationen_US
dc.subjectIsolated neutral networken_US
dc.subjectLow voltage secondary substationen_US
dc.titleAn earth fault location scheme for isolated and compensated neutral distribution systemsen_US
dc.typeArticleen_US
dc.contributor.urlmohdrafi.adzman@aalto.fien_US
dc.contributor.urlmohdrafi@unimap.edu.myen_US
dc.contributor.urltopolanek@feec.vutbr.czen_US
dc.contributor.urlmatti.lehtonen@aalto.fien_US
dc.contributor.urltoman@feec.vutbr.czen_US
Appears in Collections:School of Electrical Systems Engineering (Articles)

Files in This Item:
File Description SizeFormat 
An earth fault location scheme for isolated and compensated neutral distribution systems.pdf34.08 kBAdobe PDFView/Open


Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.