Please use this identifier to cite or link to this item: http://dspace.unimap.edu.my:80/xmlui/handle/123456789/22908
Title: A method for ground fault distance computation in unearthed medium voltage distribution network
Authors: Mohd Rafi, Adzman
Lehtonen, Matti
mohdrafi@unimap.edu.my
Keywords: Charge transient
Fault location
Impedance matrix
Unearthed network
Issue Date: 2012
Publisher: Praise Worthy Prize S.r.l.
Citation: International Review on Modelling and Simulations, vol. 5 (4), 2012, pages 1765-1772
Abstract: In networks with unearthed or compensated neutral, earth fault signals consist of different frequency components, which result from charging and discharging of the network capacitances. The charge transient which usually is of higher amplitude and lower frequency than the discharge transient is most suitable for fault location. This paper discusses a method for estimating a single phase to ground fault location in radially operated unearthed distribution network. The proposed method is based on correlation of undamped charge transient frequency with the fault distance. The undamped complex frequency is defined from the development of single phase to ground fault bus impedance matrix of the circuit network in complex frequency domain. The accuracy of the method was tested using a simulation model and the network example with overhead lines. The analysis was performed using the EMTP-ATP software.
Description: Link to publisher's homepage at http://www.praiseworthyprize.it/
URI: http://www.praiseworthyprize.it/public/SUBSCRIBERS/IREMOS.html
http://dspace.unimap.edu.my/123456789/22908
ISSN: 1974-9821
Appears in Collections:School of Electrical Systems Engineering (Articles)

Files in This Item:
File Description SizeFormat 
a method.pdf32.86 kBAdobe PDFView/Open


Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.