Please use this identifier to cite or link to this item:
http://dspace.unimap.edu.my:80/xmlui/handle/123456789/2197
Full metadata record
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Ismail, Daut | |
dc.contributor.author | Dina Maizana, Maiz Ahmad | |
dc.contributor.author | Shuhaimi, Zakaria | |
dc.contributor.author | Soib, Taib | |
dc.date.accessioned | 2008-09-15T01:13:14Z | |
dc.date.available | 2008-09-15T01:13:14Z | |
dc.date.issued | 2007-12-13 | |
dc.identifier.uri | http://dspace.unimap.edu.my/123456789/2197 | |
dc.description | Organized by Universiti Kuala Lumpur (UniKL), 11th - 13th December 2007 at Kuala Lumpur, Malaysia. | en_US |
dc.description.abstract | This paper describes the results of an investigarion on the effect of different amount of layers per stack of core lamination in the three of 3 phase distribution transformers 1000kVA. The investigation involves the variant of power loss, building factor, total harmonic distortion of flux and flux leakages. The power loss and flux distribution have been measured using no load test in three types of model of setting of core built from the same size and type of M5 (CGO) laminations. The power loss of the transformer core assembled with 1 layer per stack of lamination is 7% better than the power loss of the transformer core assembled with 2 layer per stack of lamination and is also 9% better than the power loss of the transformer core assembled with 3 layers per stack of lamination, at 1.7T, 50 Hz. The flux leakage at the corner joint in the core assembled with 1 layer per stack of lamination is the lowest among the three of the transformer cores, over the whole flux density range. Total harmonic distortion flux is the largest in the transformer core with 3 layers per stack of lamination and smallest in the transformer core with 1 layer per stack lamination. Using 1 layer per stack of lamination of the transformer core. | en_US |
dc.language.iso | en | en_US |
dc.publisher | Universiti Kuala Lumpur (UniKL) | en_US |
dc.relation.ispartofseries | International Conference on Engineering Technology 2007 (ICET 2007) | en_US |
dc.subject | Transformer core | en_US |
dc.subject | Flux distribution | en_US |
dc.subject | Harmonic flux | en_US |
dc.subject | Power loss | en_US |
dc.subject | Building Factor (BF) | en_US |
dc.subject | Transformers | en_US |
dc.subject | Electronics transformers | en_US |
dc.subject | Electric transformers | en_US |
dc.title | Comparison on losses and flux distribution among three 3-phase distribution transformers 1000kVA assembled from various amount of layers per stack of transformers core lamination | en_US |
dc.type | Working Paper | en_US |
Appears in Collections: | Conference Papers Ismail Daut, Prof. Dr. |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Comparison on Losses and Flux Distribution among Three 3-Phase Distribution Transformers 1000kVA Assembled from Various Amount of Layers per stack of Transformer Core Lamination.pdf | Access is limited to UniMAP community. | 1.89 MB | Adobe PDF | View/Open |
Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.