Please use this identifier to cite or link to this item: http://dspace.unimap.edu.my:80/xmlui/handle/123456789/2197
Full metadata record
DC FieldValueLanguage
dc.contributor.authorIsmail, Daut
dc.contributor.authorDina Maizana, Maiz Ahmad
dc.contributor.authorShuhaimi, Zakaria
dc.contributor.authorSoib, Taib
dc.date.accessioned2008-09-15T01:13:14Z
dc.date.available2008-09-15T01:13:14Z
dc.date.issued2007-12-13
dc.identifier.urihttp://dspace.unimap.edu.my/123456789/2197
dc.descriptionOrganized by Universiti Kuala Lumpur (UniKL), 11th - 13th December 2007 at Kuala Lumpur, Malaysia.en_US
dc.description.abstractThis paper describes the results of an investigarion on the effect of different amount of layers per stack of core lamination in the three of 3 phase distribution transformers 1000kVA. The investigation involves the variant of power loss, building factor, total harmonic distortion of flux and flux leakages. The power loss and flux distribution have been measured using no load test in three types of model of setting of core built from the same size and type of M5 (CGO) laminations. The power loss of the transformer core assembled with 1 layer per stack of lamination is 7% better than the power loss of the transformer core assembled with 2 layer per stack of lamination and is also 9% better than the power loss of the transformer core assembled with 3 layers per stack of lamination, at 1.7T, 50 Hz. The flux leakage at the corner joint in the core assembled with 1 layer per stack of lamination is the lowest among the three of the transformer cores, over the whole flux density range. Total harmonic distortion flux is the largest in the transformer core with 3 layers per stack of lamination and smallest in the transformer core with 1 layer per stack lamination. Using 1 layer per stack of lamination of the transformer core.en_US
dc.language.isoenen_US
dc.publisherUniversiti Kuala Lumpur (UniKL)en_US
dc.relation.ispartofseriesInternational Conference on Engineering Technology 2007 (ICET 2007)en_US
dc.subjectTransformer coreen_US
dc.subjectFlux distributionen_US
dc.subjectHarmonic fluxen_US
dc.subjectPower lossen_US
dc.subjectBuilding Factor (BF)en_US
dc.subjectTransformersen_US
dc.subjectElectronics transformersen_US
dc.subjectElectric transformersen_US
dc.titleComparison on losses and flux distribution among three 3-phase distribution transformers 1000kVA assembled from various amount of layers per stack of transformers core laminationen_US
dc.typeWorking Paperen_US
Appears in Collections:Conference Papers
Ismail Daut, Prof. Dr.



Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.