dc.descriptionLink to publisher's homepage at http://ieeexplore.ieee.org/en_US
dc.description.abstractThis paper describes the result of investigation of longitudinal direction of flux distribution in 100kVA 3phase distribution transformer assembled with the mix 60° - 23° in different layers of T-joint. The measurement involves the fundamental and third harmonic of the easy and hard direction of flux density at each location measurement. The flux distributions have been measured using no load test by arrays of search coil in MS (CGO) grades material of transformer core laminations. The localised flux density at the outer the mix 60° 23° in different layers of T-joint is 1.4T and rises to be 1.7T at the inner edges of the mix60° - 23° in different layers of T-joint when the transformer core energized 1.5 T 50Hz. Harmonic occurs mostly in the T-joint where local regions are saturated and the flux deviates from the rolling direction.A small amount of flux deviation from the rolling direction occurs at the overlap, but no rotational flux is present in the joint.en_US
dc.language.isoenen_US
dc.publisherInstitute of Electrical and Electronics Engineers (IEEE)en_US
dc.relation.ispartofseriesProceedings of the 4th International Power Engineering and Optimization Conference (PEOCO) 2010en_US
dc.subjectSearch coilen_US
dc.subjectThe in-plane flux distributionen_US
dc.subjectThird harmonicen_US
dc.subjectTransformer coreen_US
dc.titleInfluence of the Mix 60° - 23° in different layers of T-joint of 3phase transformer core on longitudinal direction of flux distributionen_US
dc.typeWorking Paperen_US
dc.contributor.urldina@unimap.edu.myen_US
dc.contributor.urlfijay@unimap.edu.myen_US
Appears in Collections:Conference Papers

Files in This Item:
File Description SizeFormat 
Influence of the Mix 60.pdf43.33 kBAdobe PDFView/Open


Items in UniMAP Library Digital Repository are protected by copyright, with all rights reserved, unless otherwise indicated.